Shop
Support
Community
TechCenter
Home
Topics: All
Wikis
Forums
Blogs
Video
TechChat
Events
About
TechCenter
Dell Community
Search Options
Search Everything
Search TechCenter Chats
TechCenter
>
TechCenter Extras
>
TechCenter Chats
>
TechCenter Chats - Wiki
>
01-08-2008 Chat Log
Join
Sign in
01-08-2008 Chat Log
TechCenter Chats
Home
Wiki
Group and Wiki Navigation
Loading...
Search
Article
History
01-08-2008 Chat Log
TechCenter Chats - Wiki
Transcript of Dell 10G Eval Wiki Web Chat of 1/8/08 (edited for brevity, clarity and accuracy)
DELL-davej
I'd like to welcome everyone to the 4th Dell 10G Blades Eval Wiki Web Chat
DELL-davej
There are 3 things I wish to cover about Power Management on the 10G Blades: Power Supply redundancy, Dynamic Power Supply Engagement and Server Power Throttling
DELL-davej
The best source I've found so far is the CMC document (CMC Users Guide Draft.pdf) available from the Eval FTP site (customers need to ask their account teams to get them it)
DELL-davej
Let's talk about Power Supply redundancy. Production M1000e blade chassis will ship with either 3 or 6 power supply units (PSUs). With 6 you get full AC redundancy.
DELL-davej
That is, you should connect 3 PSUs to one AC grid in your data center and the other 3 PSUs to a second grid. So if you lose one grid you still have enough power to run your blades
DELL-davej
With 3 PSUs you get DC redundancy. If one should fail you can still run off of two
DELL-davej
In fact you can set a mode called Dynamic Power Supply Engagement, that will put one of the 3 PSUs in Standby if not needed
DELL-davej
If you have all 6 PSUs Dynamic Power Supply Engagement can put 2 PSUs in Standby
DELL-davej
You also have the ability to define power thresholds. The idea behind the threshold is, if you have limited power in your data center, you can control the amount that your blades draw
DELL-Todd_Muirhead
How much power can be saved by putting 2 of the 6 in standby mode?
DELL-davej
That's a good question because the PSUs themselves are very efficient.
DELL-davej
Let me give you some numbers: at idle I am seeing each of the four blades draw about 150W, and the entire chassis is drawing 900W
DELL-davej
So the chassis, including PSUs, CMC, iKVM and IOMs is only drawing 300W total
DELL-davej
The CMC has some powerful algorithms to monitor power consumption by all the blades and limit power to individual blades in a prioritized fashion if there is not enough power available
DELL-davej
I was going to try to play with that by setting an artifically low threshold but the lowest I can go is 2100W (this is hardcoded)
DELL-davej
The blades draw about 200W at 80% utilzation so I can't drive the 4-blade chassis above about 1100W
DELL-davej
So we'll leave that as an exercise for the interested student!
DELL-davej
BTW the term used for the CMC limiting the power to a blade is what I mentioned earlier, Server Power Throttling
DELL-davej
All of this is controlled through the CMC (using either the GUI or racadm CLI) but you have to go into the individual blade iDRACs to see how much power they are consuming
DELL-ScottH
How does the power limiting to the blades work ? Does it not power up the blade, or does it have a way of throttling the CPU and such ?
DELL-davej
It definitely will prevent a blade from powering up if there is insufficent power but it also will decrease power to a blade dynamically if necessary
DELL-davej
The iDRAC detects the lower power and ratchets down the CPU speed
DELL-davej
The blades start off with a power budget (310W for the Intel systems with 2 quadcore chips and 297W for the AMD blades with 2 dualcore chips)
DELL-davej
So their budgets could be throttled quite a bit before affecting performance
DELL-davej
I think those power budget values are calculated based on blade components. I haven't found a place to set them.
DELL-davej
There's some nice power stuff in the iDRAC (again, accessible through the GUI or racadm). There is total KWH consumed, and peak power and amperage. All can be reset with a button click
DELL-RogerF
Can you set preferences or priorities on which blades if any get throttled back first?
DELL-davej
Yes
DELL-Todd_Muirhead
Can the power consumed be viewed in IT Assistant console?
DELL-ScottH
There's a power monitoring task in the new ITA 8.1 (with OM 5.3) , lets you set thresholds and limits and sends alerts ...
DELL-ScottH
but the new tab for "Performance and Power" in the Devices interface doesn't show up on our blade system.
DELL-ScottH
Need to get the MLK systems in and see what shows up for power
DELL-davej
I forgot to mention that each PSU can provide 2360W. So 3 PSUs should be able to easily handle 16 blades
DELL-RogerF
Are there any options for dynamic throttling preferences i.e. low CPU utilization blades first?
DELL-davej
No. You can only designate a number from 1 to 10 (1 being highest priority). It will start throttling the lowest priority first. In the case of a tie it will do the lower blade position first.